Disk¯1;(6)Green Power Technology description¯1;(7)Battery Charger¯1;(8)Cable Collector¯1
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1. Insure that the equipment plugged into the battery power-supplied outlets does not exceed the UPS
unit’s rated capacity (450VA/270W for BR450ELCD, 650VA/390W for BR650ELCD, 850VA/510W for
BR850ELCD). If rated unit capacities are exceeded, an overload condition may occur and cause the
UPS unit to shut down or the fuse blow.
2. If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert
Watts (W) or Amps (A) into VA by doing the calculations below. Note: The below equation only
calculates the maximum amount of VA that the equipment can use, not what is typically used by the
equipment at any one time. Users should expect usage requirements to be approximately 60% of
below value.
TO ESTIMATE POWER REQUIREMENTS
1.
Watts (W) x 1.67 = VA or Amps (A) x 230 = VA
2. Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate actual
requirements. There are many factors that can affect the amount of power that your computer system
will require.Suggest the total load to be placed on the battery-powered outlets should not exceed
80% of the unit’s capacity.
HARDWARE INSTALLATION GUIDE
Before installation, please
read and understand the following instructions:
1. Placement
The UPS must be installed in a protected environment away from heat- emitting appliances such
as a radiator or heat register. Do not install this product where excessive moisture is present.
2. Ventilation
The location should provide adequate air flow around the UPS with one inch minimum clearance
on all sides for proper ventilation.
3. Charge the Battery
Your new UPS may be used immediately upon receipt. However charge loss may occur during
shipping and storage. So charging the battery for at least 8 hours is recommended to insure that
the battery is fully charged. (To recharge the battery, simply leave the unit plugged into an AC
outlet.)
This UPS can be charged even when UPS is not turn on.
4. Connect to AC
Use power cord to connect
the UPS to a wall outlet. Please avoid
using extension cords and adapter
plugs. (To maintain optimal battery
charge, leave the UPS plugged in at
all times.)
5. Connect the Load
Connect the equipment to your UPS
outlets. The IEC power cord coming
with the unit are used to connect your
computer and monitor to the UPS.
Items such as copiers, laser
printers, vacuums, space heaters,
or other large electrical devices
SHOULD NOT be connected to the
UPS. Please make sure that the total
loads of your equipments are less than the maximum total power load of your UPS.
6. Connect to Computer
Install your software and accessories. To use the software, simply use the USB cable to connect
the UPS unit and your computer.
BASIC OPERATION
1. Power On/Off Switch
Press the power switch to turn the UPS ON or OFF.
2. LCD Function Selected Switch
Press the LCD function selected switch to know the UPS status.
3. LCD Display
The LCD will display the UPS status including input voltage, output voltage, runtime, percentage of
load and battery…etc.
4. Communication Protection Ports RJ11/RJ45
Communication protection ports will protect any standard modem, fax, telephone line, or network
cable from surge and spikes.
5. Battery Charger port
Charge external AA/AAA battery via battery charger port with battery charger.
6. AC outlet
The UPS provides 3 outlets for connected equipment to insure temporary uninterrupted operation
during a power failure and against surges and spikes and another 3 outlets against surges and spikes
only.
7. USB Port to PC
This port allows connection andcommunication
from the USB port on the computer to the UPS
unit. The UPS communicates its status to the
PowerPanel
®
Personal Edition software. This
interface is also compatible with the UPS service
provided by Windows NT, Windows 2000,
Windows XP, Windows Vista. Mac OSX, Linux.
8. Input Circuit Breaker
The Circuit Breaker provides optimal overload protection.
9 Power on LED
The power on LED lights up when the UPS is ON.
10 Cable Collector
Collect the cables connected from the AC outlets in the cable collector.
11 Battery Charger
Put external AA/AAA batteries into the battery charger for charge.
Whatsapp
Mail
Facebook
Behöver du hjälp?
Antal frågor: 0
Behöver du hjälp eller har du en fråga om CyberPower BR450ELCD? Ställ din fråga här. Lämna en tydlig och omfattande beskrivning av ditt problem och din fråga. Ju mer information du anger desto enklare blir det för andra ägare av CyberPower BR450ELCD att svara på din fråga.
Om CyberPower BR450ELCD
+1
Se manualen för CyberPower BR450ELCD helt gratis här nedan. Den här manualen tillhör kategorin och har betygsatts av 1 personer med ett genomsnitt på 7.5. Den här manualen är tillgänglig på följande språk: Engels. Behöver du hjälp eller har du en fråga om CyberPower BR450ELCD? Ställ din fråga här
Vi använder cookies för att se till att vi ger dig den bästa upplevelsen på vår hemsida. Om du fortsätter att använda den här webbplatsen kommer vi att anta att du godkänner detta.