CyberPower CP600LCD

CyberPower CP600LCD bruksanvisning

(1)
  • 10
    11
    12
    1
    3
    1
    22
    9
    6 6
    7
    8
    8
    5
    4
    Problem Possible Cause Solution
    Full-time surge protection outlets
    stop providing power to
    equipment. Circuit breaker
    button is projecting from the side
    of the unit.
    Circuit breaker has tripped due to an
    overload.
    Turn the UPS off and unplug at least one piece of equipment.
    Wait 10 seconds, reset the circuit breaker by depressing the
    button, and then turn the UPS on.
    Battery is not fully charged Recharge the battery by leaving the UPS plugged in.
    The UPS does not perform
    expected runtime.
    Battery is slightly worn out.
    Contact CyberPower Systems about replacement batteries at
    tech@cyberpowersystems.com
    The on/off switch is designed to
    prevent damage by rapidly turning it
    off and on.
    Turn the UPS off. Wait 10 seconds and then turn the UPS on.
    The unit is not connected to an AC
    outlet.
    The unit must be connected to a 110/120v 60Hz outlet.
    The battery is worn out.
    Contact CyberPower Systems about replacement batteries at
    tech@cyberpowersystems.com
    The UPS will not turn on.
    Mechanical problem.
    Contact CyberPower Systems at
    tech@cyberpowersystems.com
    UNPACKING
    Inspect the UPS upon receipt. The box should contain the following:
    (1) UPS unit; (1) User's manual; (1) PowerPanel Personal Edition software CD; (1) USB device cable; (1) Telephone cable; (1)
    Warranty registration card
    HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
    1. Make sure that the total Volt-Amp (VA) requirements of your computer, monitor and peripheral equipments does not exceed
    rated VA as spec.
    2. Ensure that the equipment plugged into the four battery power-supplied outlets does not exceed the UPS unit's rated capacity
    . If rated unit capacities are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit
    breaker to trip.
    3. If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert Watts (W) or Amps (A) into
    VA by doing the calculations below. Note: The below equation only calculates the maximum amount of VA that the equipment
    can use, not what is typically used by the equipment at any one time. Users should expect actual usage values to be
    approximately 60% of the calculated values.
    Watts (W) x 1.67 = VA or Amps (A) x 120 = VA
    Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate actual power requirements.
    There are many factors that can affect the amount of power that your computer system will require. The total load that you will
    be placing on the battery-powered outlets should not exceed 80% of the unit's capacity.
    HARDWARE INSTALLATION GUIDE
    1. Your new UPS may be used immediately upon receipt. However, recharging
    the battery for at least 16 hours is recommended to ensure that the battery's
    maximum charge capacity is achieved. A loss of charge may occur during
    shipping and storage. To recharge the battery, simply leave the unit plugged
    into an AC outlet. The unit will charge in both the ON as well as the OFF
    position. If you wish to use the software, use the enclosed USB devices cable
    to connect the UPS to your computer. If you are not going to use the
    software, you do not need to connect the cable.
    2. With the UPS unit turned off and unplugged, connect your computer, monitor and any externally powered data storage device
    (Zip drive, Jazz drive, Tape drive, etcƦ) into the battery power supplied outlets. Plug your peripheral equipment (printer,
    scanner, speakers) into the full-time surge protection outlets. DO NOT plug a laser printer, paper shredder, copier, space
    heater, vacuum or other large electrical device into the UPS. The power demands of these devices will overload and
    possibly damage the unit.
    3. To protect a fax, phone or modem, connect a telephone cable from the wall jack outlet to the “in” jack of the UPS. Connect a
    telephone cable from the “out” jack with the CPU icon to the modem port on your computer. The “out” jack with the telephone
    icon can be used to protect a telephone or fax machine.
    4. Plug the UPS into a 2 pole, 3 wire grounding receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse
    or circuit breaker and does not service equipment with large electrical demands (e.g. refrigerator, copier, etcƦ). The warranty
    prohibits the use of extension cords, outlet strips, and surge strips.
    5. Press the power switch to turn the unit on. The power on indicator light will illuminate and the unit will "beep" once.
    6. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off
    and unplug at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the circuit
    breaker is depressed and then turn the UPS on.
    7. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will automatically
    recharge.
    8. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
    9. To store your UPS for an extended period, cover it and store with the battery fully charged. While in storage recharge the
    battery every three months to insure battery life.
    Circuit Breaker
    Located on the side of the UPS, the circuit breaker serves to provide overload and fault protection.
    Software Communication Port
    The port allows connection and communication from the USB on the computer to the UPS unit. The UPS communicates its
    status to the PowerPanel Personal Edition software. This interface is also compatible with the Power Management
    provided by Windows 2000 and Windows XP.
    Note: To install PowerPanel Personal Edition Software the computer will need Microsoft Internet Explore 5.0 or higher
    installed.
    Outlets Designed for AC Transformer
    The unit has four Transformer Spaced Outlets blocks to be plugged into the UPS without blocking adjacent outlets.
    Vertical Use Stand
    The unit can be placed on it end in a vertical orientation.
    Note: We recommend you place the unit next to the wall when standing the unit vertically.
    LCD Module Display
    High resoluation and intelligent LCD panel shows all the UPS information with icons and messages. For more information
    please check the "Definitions for Illuminated LCD Indicators" section.
    LCD panel Toggle/Selected Switch
    The switch can be used to select the LCD panel contents including Input Voltage, Output Voltage and Estimated Run Time.
    The toggle frequency is set to one time per second. Holding the switch for more than two seconds while running on battery
    will silence the buzzer.
    8
    9
    10
    11
    12
    R
    R
    R
    R
    R
    R
    (SAVE THESE INSTRUCTIONS)
    This manual contains important safety instructions. Please read and follow all instructions carefully during installation and
    operation of the unit. Read this manual thoroughly before attempting to unpack, install, or operate your UPS.
    CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of
    conductive contaminants. (Please see specifications for acceptable temperature and humidity range).
    CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. No user serviceable parts
    are inside except for battery.
    CAUTION! Some components can be energized by the battery even when the AC input power is disconnected.
    CAUTION! UPS must be connected to an AC power outlet which has a fuse or is connected to a circuit breaker. Do not plug into
    an outlet that is not grounded.
    CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or
    installing a computer component.
    DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support or
    medical applications. DO NOT use in any circumstance that would affect operation or safety of any life support equipment or with
    any medical applications or patient care.
    DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium.
    Condensation from the aquarium can cause the unit to short out.
    DO NOT USE WITH LASER PRINTERS! The power demands of these devices will overload and possibly damage the unit.
    REPLACING THE BATTERY
    CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under
    the supervision of personnel knowledgeable of batteries and their precautions.
    CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
    CAUTION! The battery may present a risk of electrical shock. Do not dispose of battery in a fire as it may explode. Follow all
    local ordinances regarding proper disposal of batteries. Almost any retailer that sells lead-acid batteries collects used batteries
    for recycling, as required by most state laws.
    CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes and may be toxic.
    CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the following precautions before
    replacing the battery:
    1. Remove all watches, rings or other metal objects.
    2. Only use tools with insulated handles.
    3. Do not lay tools or metal parts on top of battery or any terminals.
    4. Wear rubber gloves and boots.
    5. Determine if the battery is inadvertently grounded. If grounded, remove the source of ground. CONTACT WITH GROUNDED
    BATTERY CAN RESULT IN ELECTRICAL SHOCK!
    TO REPLACE THE BATTERY
    1. Turn off and unplug all connected equipment.
    2. Turn the UPS off and unplug it from the AC power source.
    3. Turn the UPS upside down.
    4. Remove the 1 retaining screw.
    5. Slide the battery compartment cover completely off of the unit.
    6. Remove the battery from the compartment.
    7. Disconnect the battery wires from the battery.
    8. Install the replacement battery by connecting the red wire and black wire to the positive (+) and negative (-) terminal of the
    battery.
    9. Put the battery back into the compartment.
    10. Slide back the battery compartment cover and tighten the retaining screw.
    11. Recharge the unit for 4 - 8 hours to fully charge the battery.
    REMINDER: Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Almost any retailer that sells
    lead-acid batteries collects used batteries for recycling, as required by most state laws.
    CP600/785/825LCD
    User's Manual
    DEFINITIONS FOR ILLUMINATED LCD INDICATORS
    INPUT voltage meter: This meter measures the AC voltage that the UPS system
    is receiving from the utility wall outlet. The UPS is designed, through the use of
    automatic voltage regulation, to continuously supply connected equipment with
    stable, 110/120 output voltage. In the event of a complete power loss, severe
    brownout, or over-voltage, the UPS relies on its internal battery to supply
    consistent 110/120 output voltage. The INPUT voltage meter can be used as a
    diagnostic tool to identify poor-quality input power.
    OUTPUT voltage meter: This meter measures, in real time, the AC voltage that
    the UPS system is providing to the computer, such as normal line mode, and
    battery backup mode.
    Note: The OUTPUT voltage meter shows the status of the battery backup outlets.
    ESTIMATE RUN TIME: This displays the run time estimate of the UPS with the
    current battery capacity and load.
    NORMAL icon: This icon appears when the UPS is working under normal conditions.
    BATTERY icon: During a severe brownout or blackout, this icon appears and an alarm sounds (two short beeps followed by a
    pause) to indicate the UPS is operating from its internal batteries. During a prolonged brownout or blackout, the alarm will sound
    continuously (and the BATT.CAPACITY meter shows one 20% capacity segment shaded) to indicate the UPS's batteries are
    nearly out of power. You should save files and turm off your equipment immediately.
    OVER LOAD icon: This icon appears and an alarm sounds to indicate the battery-supplied outlets are overloaded. To clear the
    overload, unplug some of your equipment from the battery-supplied outlets until the icon turns off and the alarm stops.
    BATT. CAPACITY meter: This meter displays the approximate charge level (in 20% increments) of the UPS?s internal battery.
    During a blackout or severe brownout, the UPS switches to battery power, the BATTERY icon appears, and the charge level
    decreases.
    LOAD CAPACITY meter: This meter displays the approximate output load level (in 20% increments) of the UPS?s battery
    outlets.
    The LCD display indicates a variety of
    UPS operational conditions. All
    descriptions apply when the UPS is
    plugged into an AC outlet and turned
    on or when the UPS is on battery.
    1
    2
    3
    4
    5
    6
    Battery and Surge Protected Outlets
    The unit has four battery powered/surge protected
    outlets for connected equipments and ensures
    temporary uninterrupted operation of your
    equipment during a power failure.
    Full-Time Surge Protection Outlets
    The unit has four always on surge suppression
    outlets.
    Power Switch
    Can be used as a master on/off switch for
    equipment connected to the battery power supplied
    outlets
    Power On Indicator
    This LED is illuminated when the utility condition is normal and the UPS outlets are providing power, free of surges and
    spikes.
    Electrical Wiring Fault Indicator
    This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missing ground or
    reversed wiring. If this is illuminated, user is advised to disconnect all electrical equipment from the outlet and have an
    electrician check to ensure the outlet is properly wired. The unit will not provide surge protection without being plugged into
    a grounded and properly wired wall outlet.
    Communication Protection Ports
    Communication protection ports will protect any standard modem, fax or telephone line.
    DESCRIPTION
    BASIC OPERATION
    INSTALLING YOUR UPS SYSTEM
    IMPORTANT SAFETY WARNINGS
    TROUBLE SHOOTING
    7
    P/N: K01-0000016-00
CyberPower CP600LCD

Behöver du hjälp?

Antal frågor: 0

Behöver du hjälp eller har du en fråga om CyberPower CP600LCD? Ställ din fråga här. Lämna en tydlig och omfattande beskrivning av ditt problem och din fråga. Ju mer information du anger desto enklare blir det för andra ägare av CyberPower CP600LCD att svara på din fråga.

Se manualen för CyberPower CP600LCD helt gratis här nedan. Den här manualen tillhör kategorin och har betygsatts av 1 personer med ett genomsnitt på 9.6. Den här manualen är tillgänglig på följande språk: Engelsk. Behöver du hjälp eller har du en fråga om CyberPower CP600LCD? Ställ din fråga här

CyberPower CP600LCD – specifikationer

Allmänt
Varumärke CyberPower
Modell CP600LCD
Produkt Avbrottsfri strömförsörjning (UPS)
EAN 41113741022, 64953201600, 649532016006, 6495320160062, 887603046181
Språk Engelsk
Filtyp PDF
Egenskaper
Uteffekt kapacitet (VA) 600
Uteffekt 340
Energivärdering 1030
Ingångsfrekvens 60
Högsta strömstyrka -
Svarstid (medel) 4
Hörbart larm
UPS-topologi Vänteläge (offline)
Övrigt
Anslutningsdetaljer utgång NEMA 5-15R
Anslutningsdetaljer ingång NEMA 5-15P
Produktstorlek (BxDxH) 279.4 x 165.1 x 89
Vikt (imperial) 14
Omgivningstemperatur vid drift 32 - 95
Dimension (B x D x H) (imperial) 11 x 3.5 x 6.5
Batteri
Normal drifttid vid halv belastning 9
Normal drifttid vid full belastning 2
Laddningstid 8
Utbytbara batteripatroner BB - SH1228W
Anslutningar
Modem (RJ-11) portar 1
Antal LAN (RJ-45) anslutningar 1
Antal USB 2.0 anslutningar 1
Vikt & dimension
Vikt 6350
Miljökrav
Temperatur vid drift 0 - 40
Intervall för relativ operativ luftfuktighet 0 - 95
Design
Certifiering UL1778, cUL 107.1, FCC DOC Class B

Bruksanvisni.ng

Letar du efter en manual? Bruksanvisni.ng säkerställer att du hittar manualen som du letar efter på nolltid. Vår databas innehåller mer än 1 miljon PDF-manualer från över 10 000 märken. Varje dag lägger vi till de senaste manualerna så att du alltid hittar produkten du letar efter. Det är väldigt enkelt: ange bara märket och typen av produkt i sökrutan för att omedelbart semanualen du önskar online helt gratis.

Bruksanvisni.ng

© Copyright 2020 Bruksanvisni.ng. All Rights Reserved.

Vi använder cookies för att se till att vi ger dig den bästa upplevelsen på vår hemsida. Om du fortsätter att använda den här webbplatsen kommer vi att anta att du godkänner detta.

Läs mer