CyberPower OR700LCDRM1U

CyberPower OR700LCDRM1U bruksanvisning

(1)
  • Automatic Voltage Regulators
    increase low or decrease high voltage to a computer
    safe 110/120 volts. The AVR automatically provides
    battery back-up power if line voltage drops below 90
    volts or exceeds 140 volts.
    AVR
    INCONSISTENT
    UTILITY POWER
    CONSISTENT
    SAFE POWER
    1 2 3 4
    5 6
    UNINTERRUPTIBLE
    POWER SUPPLY
    E187679
    6G48
    IN
    AC INPUT
    Push To
    RESET
    WIRING
    FAULT
    OUT
    SERIAL
    13 7 8 9 10 11 12
    INSPECTION
    The box should contain the following:
    (1) PowerPanel
    ®
    Business Edition software (CD); (1) RS232 cable (DB-9); (1) USB cable (A+B type); (1) Telephone communication cable;
    (1) user manual; (1) Warranty registration card; (1) UPS unit.
    OVERVIEW
    The OR500LCDRM1U/OR700LCDRM1U provides automatic voltage regulation for inconsistent utility
    power. The OR500LCDRM1U/OR700LCDRM1U features 1030 Joules of surge protection, and provides
    battery backup during power outages. The OR500LCDRM1U/OR700LCDRM1U ensures consistent
    power to your computer system and its included software will automatically save your open files and
    shutdown your computer system during a utility power loss.
    AUTOMATIC VOLTAGE REGULATOR
    The OR500LCDRM1U/OR700LCDRM1U stabilizes inconsistent utility power. The incoming utility power
    may be damaging to important data files, but with Automatic Voltage Regulation, the computer will not
    experience damaging voltage levels. An Automatic Voltage Regulator automatically increases low or decreases high voltage to a consistent,
    computer safe 110v/120v. The unit’s powerful sealed lead-acid batteries will provide power only if the incoming voltage drops below 90v or
    increases above 140v.
    HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
    1. Make sure that the total Volt-Amp (VA) requirements of your computer, monitor, and peripheral equipment does not exceed 500 VA/
    700VA.
    2. Ensure that the equipment plugged into the four battery power-supplied/surge outlets does not exceed the UPS unit¡¦s rated capacity
    (500VA/300W for OR500, 700VA//400W for OR700). If the rated unit capacities are exceeded, an overload condition may occur and cause
    the UPS unit to shut down and the circuit breaker to trip.
    3. If the power requirements of your equipment are listed in units other than Volt-Amps (VA), convert Watts (W) or Amps (A) into VA by
    performing the calculations below. Note: The equation listed below only calculates the maximum amount of VA that the equipment can use,
    not what is typically used by the equipment at given time. Users should expect usage requirements to be approximately 60% of the
    maximum power requirements:
    Watts (W) x 1.82 = VA or Amps (A) x 120 = VA
    Add the totals up for all pieces of equipment and multiply this total by 0.6 to calculate the approximate requirements.
    There are many factors that can affect the amount of power that your computer system will require. The total load that you will be placing on
    the battery-powered outlets should not exceed 80% of the unit's capacity.
    Office Rack Mount UPS
    OR500LCDRM1U/OR700LCDRM1U
    User’s Manual
    K01-0000030-00
    In purchasing a OR500 / OR700 in the United States or Canada, the original end user receives a Limited Warranty and CyberPower's
    Power Control Guarantee from Cyber Power Systems (USA), Inc. (for ease of reading, referred to as "CyberPower"). The Limited Warranty
    and the Power Control Guarantee are intended to be the original end-user's exclusive rights and remedies. The Limited Warranty and the
    Power Control Guarantee are separate, all though they are related. The Limited Warranty is for the Product itself. The Power Control
    Guaranty is CyberPower¡¦s connected equipment guaranty.
    Limited Warranty. The original end user (referred to as the "Initial Customer") receives an express limited warranty (referred to as the
    "Limited Warranty") for the OR500 / OR700 purchased from CyberPower (referred to as the "Product"). The terms of the Limited Warranty
    are explained below.
    Power Control Guarantee. CyberPower provides the Initial Customer with protection in the event that the Product is not free from defects
    in materials and workmanship, and certain equipment connected to the Product is damaged (the "Power Control Guarantee"). The Power
    Control Guarantee protects the Initial Customer for damage to equipment plugged into the Product. The terms of the Power Control
    Guarantee are explained below.
    The Limited Warranty and the Power Control Guarantee are subject to the terms set forth below. Additionally, State or Provincial law may
    adjust the terms of the Limited Warranty or the Power Control Guarantee or the State or Province may impose additional obligations, or
    additional "implied warranties." To the extent necessary to comply with those laws, the terms of the Limited Warranty and the Power Control
    Guarantee should be read to adjust to those requirements only to the extent necessary to comply with such local law.
    If you are an Initial Customer, you are asked to read the following terms and conditions carefully before using the Product. By using the
    Product you consent to be bound by and become a party to the Limited Warranty and Power Control Guarantee. If you do not agree to the
    terms and conditions of the Limited Warranty and Power Control Guarantee, you should return the Product for a full refund prior to using it.
    REGISTRATION
    CyberPower requests that you complete and return the Warranty Registration Card enclosed with the Product or register the Product at its
    website (www.cyberpowersystems.com) to establish that you are the Initial Customer of the Product, and therefore entitled coverage under
    the Limited Warranty and the Power Control Guarantee. (Registration is not required for Limited Warranty coverage, but note if you do not
    complete a registration card you will be required to provide proof of purchase, as described below, to have the benefits of this Limited
    Warranty.)
    LIMITED WARRANTY
    CyberPower warrants to you, the Initial Purchaser, that the Product will be free from defects in material and workmanship for three years
    from the date of original purchase, subject to the terms of this Limited Warranty. This Limited Warranty gives you specific rights, and you
    may have other rights, which vary from State to State or Province to Province.
    Any Implied Warranty of Merchantability or for Fitness for a Particular Purpose, if applicable
    to the Product, is limited in duration to the period of ownership by the Initial Customer. This provision shall NOT create any Implied Warranty
    or Merchantability or of Fitness for a Particular Purpose that would not otherwise apply to the Product.
    NOTE: Some States and some Provinces do not allow limitations on how long an implied warranty lasts, so the above limitation
    may not apply to you.
    To be covered you must still be the owner of the Product at the time of the failure that results in the claim made under this Limited Warranty.
    Exclusive Remedies Under Limited Warranty.
    Your exclusive remedy and CyberPower's' sole obligations are as follows for the Product:
    If (a) the CyberPower Product you purchased and still own is defective in material or workmanship under this Limited Warranty or any
    applicable warranty imposed by law, and
    (b) all Limited Warranty requirements have been met, CyberPower will repair or replace the
    Product if it proves to be defective in material or workmanship during the Warranty Period.
    Making a Limited Warranty Claim.
    To make a Limited Warranty claim on a Product, you must do the following:
    1. Complete and return the CyberPower Warranty Registration Card, or provide reasonable proof of purchase (for example, a sales receipt)
    that establishes you as the Initial Customer (the original end-user consumer purchaser) of the Product and prove that the Product was
    purchased within three (3) years of the event for which you want to make a claim for warranty service.
    2. Call CyberPower at (952) 403-9500 or (877) 297-6937 (toll free), write to CyberPower at 5555 12th Ave. East, Suite 110, Shakopee, MN
    55379, or e-mail CyberPower at claims@cyberpowersystems.com, within ten (10) days of the event for which you want to make a claim.
    3. When you contact CyberPower, identify the Product, the Purchase Date, and request Return Materials Authorization (RMA) information
    from CyberPower.
    4. Pack and ship the Product to CyberPower as instructed in your RMA. Show the RMA code on the shipping label or include it with the
    Product. You MUST prepay all shipping costs and you are responsible for packaging and shipment.
    This manual contains important instructions that should be followed during installation and mainte-nance of the UPS and batteries. Please
    read and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to
    unpack, install, or oper-ate.
    CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into
    an outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the UPS.
    CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! Cyber-Power Systems does not sell products for life support
    or medical applications. DO NOT use in any circumstance that would affect the operation or safety of any life support equipment, with any
    medical applications, or patient care.
    CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.
    CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity con-trolled indoor area, free of conductive
    contaminants. (Please see specifications for acceptable tem-perature and humidity range).
    CAUTION! To reduce the risk of electric shock, do not remove the cover, except to service the battery. There are no user serviceable parts
    inside, except for the battery.
    CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a
    computer component.
    CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation
    from the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
    CAUTION! DO NOT USE WITH LASER PRINTERS! The power demands of laser printers are too large for a UPS.
    DESCRIPTION
    1. LCD module display
    LCD shows all the UPS information with icons and
    messages.
    2. Power On Indicator
    This LED is illuminated when the utility condition is
    normal and the UPS outlets are providing power,
    free of surges and spikes.
    3. Power Switch
    Master on/off switch for equipment connected to the
    battery power supplied outlets.
    4. LCD function selected switch
    The switch can be used to select the LCD display contents Including input/output voltage and estimated run time, etc.
    5. Battery, Surge and AVR Outlets
    Provides four battery power, surge protected and AVR outlets for connected equipment and ensures temporary uninterrupted operation of
    your equipment during a power failure.
    6. Surge Outlets
    Provides two surge protected outlets for connected equipment.
    7. Communication Protection Ports RJ11/RJ45
    Communication protection ports will protect any standard modem, fax, telephone line, or network cable .
    8. USB Port to PC
    This port allows connection and communication from the USB port on the computer to the UPS unit. The UPS communicates its status to
    the PowerPanel
    ®
    Business Edition software. This interface is also compatible with the UPS application provided by Windows Vista and Mac
    OS X.
    9. Dry contact
    This port produces information for equipment that can read dry contact signals.
    10. Circuit Breaker
    Located on the side of the UPS, the circuit breaker serves to provide overload and fault protection. Under normal operating conditions, the
    circuit breaker is depressed.
    11. Electrical Wiring Fault Indicator
    This LED indicator will illuminate to warn the user that a wiring problem exists, such as bad ground, missed ground or reversed wiring. If
    this is illuminated, disconnect all electrical equipment from the outlet and have an electrician check to ensure the outlet is properly wired.
    12. AC Input
    Connect the AC Power cord to a properly wired and grounded outlet.
    13. Expansion Port
    Allow users to add the optional SNMP card.
    CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery.
    Service the battery under the supervision of personnel knowledgeable of batteries and their
    precautions.
    CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
    CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a fire,
    as they may explode. Follow all local ordinances regarding proper disposal of batteries.
    CAUTION! Do not open or mutilate the batteries. Released electrolyte is harmful to the skin and eyes
    and may be toxic.
    CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the
    following precautions before replacing the battery:
    1. Remove all watches, rings or other metal objects.
    2. Only use tools with insulated handles.
    3. DO NOT lay tools or other metal parts on top of battery or any battery terminals.
    4. Wear rubber gloves and boots.
    5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
    source of ground. CONTACT WITH A GROUNDED BATTERY CAN RESULT IN
    ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance
    (applicable to a UPS and a remote battery supply not having a grounded circuit)
    Model OR500 OR700
    Capacity 500VA(300W) 700VA(400W)
    Input Voltage on Utility 90V to 140V
    Input Frequency 57 Hz to 63 Hz
    Line Conditioning Regulation
    AVR Max. boost 12% of input voltage for output regulation while
    input voltage is from 16% to 25% under nominal.
    On-Battery Output Voltage 120Vac +/- 10%
    On-Battery Output Wave Form Simulated Sine Wave Form
    Transfer Time 4ms Typical
    Overload Protection On Utility: Circuit Breaker, On battery: Internal Current Limiting
    Lightning / Surge Protection Yes
    Internet Ready
    (DSL/ Phone/ Fax/ Modem Protection)
    RJ11/RJ45 ( One In/ One Out )
    Operating Temperature + 32°F to 95°F. (0°C to 35°C)
    Maximum Dimensions (cm) 1U Rack 43.0 x 23.5 x 4.4
    Weight (kg) 8.2 8.4
    Typical Battery Recharge Time 8 hours typical from total discharge
    Battery Type
    Sealed Maintenance 6V 7.0AH x 2 6V 9.0AH x 2
    Free Lead Acid Battery
    User Replaceable n/a
    Indicators Power On, , Wiring Fault,
    Audible Alarms On battery, Low battery, Overload
    PowerPanel
    ®
    Business
    EditonSoftware
    Windows 98/ ME/ NT/ 2000/ XP/Vista
    Self-Test Yes
    Auto-Charge Yes
    Auto-Restart Yes
    USB Yes
    Dry contact Yes
    IMPORTANT SAFETY INSTRUCTIONS
    (SAVE THESE INSTRUCTIONS)
    INSTALLING YOUR UPS SYSTEM
    BASIC OPERATION
    Hardware Installation Guide
    TROUBLE SHOOTING
    BATTERY REPLACMENT
    CYBERPOWER GREENPOWER UPS TECHNOLOGY
    EXPECTED RUNTIME IN MINUTES
    Limited Warranty and Connected Equipment Guarantee
    TECHNICAL SPECIFICATIONS
    DEFINITIONS FOR ILLUMINATED LCD INDICATORS
    Additional troubleshooting information can be found at www.cyberpowersystems.com/support.htm
    Problem Possible Cause Solution
    Full-time surge protection
    outlets stop providing power
    to equipment.
    Circuit breaker has tripped
    due to an overload.
    Turn the UPS off and unplug at least one piece of equipment.
    Wait 10 seconds, reset the circuit breaker by depressing the
    button, and then turn the UPS on.
    The UPS does not provide
    expected runtime.
    Recharge the battery by leaving the UPS plugged in.
    Contact CyberPower Systems about replacement batteries at
    tech@cyberpowersystems.com
    Battery is slightly worn out.
    Battery not fully charged.
    The UPS will not turn on.
    The on/off switch is designed
    to prevent damage by rapidly
    turning it off and on.
    Turn the UPS off. Wait 10 seconds and then turn the UPS on.
    The battery is worn out.
    Contact CyberPower Systems about replacement batteries at
    tech@cyberpowersystems.com
    Mechanical problem.
    Contact CyberPower Systems at
    tech@cyberpowersystems.com
    PowerPanel
    ®
    Business
    Edition is inactive.
    The USB cable is not
    connected.
    Connect the USB cable to the UPS unit and an open
    USB port on the back of the computer.
    The unit is not providing
    battery power.
    Shutdown your computer and turn the UPS off. Wait 10
    seconds and turn the UPS on. This should reset the unit.
    CyberPower will inspect and examine the Product within ten (10) days of receipt. If the Product is not as warranted, CyberPower will repair
    or replace the Product and return it to you at CyberPower's expense, or, if CyberPower is unable to or decides not to repair or replace the
    Product (if defective) within a reasonable time, CyberPower will refund to you the full purchase price you paid for the Product (purchase
    receipt showing price paid is required).
    POWER CONTROL GUARANTEE
    If you are the Initial Purchaser, the Power Control Guarantee provides protection for damage to equipment connected to the Product
    ("Connected Equipment"), subject to certain terms and limitations.
    The Power Control Guarantee is not "first dollar" coverage. CyberPower's obligation is reduced by any amounts that Initial Customer is
    entitled to recover from other sources regarding the Connected Equipment, including insurance, other warranty, or extended warranty
    coverage, whether or not the Initial Customer makes a claim for recovery, including but not limited to a claim under any applicable insurance,
    other warranty, or extended warranty.
    The Limited Warranty does not cover Connected Equipment, but as is explained below, to be covered under the Power Control Guarantee,
    the Connected Equipment must have been damaged due to a failure of the Product. The Connected Equipment must have been damaged
    due to a defect in materials or workmanship of the Product.
    In the event of damage to the Connected Equipment, your exclusive remedy, and CyberPower's sole obligations are as follows for
    Connected Equipment. If (a) the Product purchased and owned by you is defective in material or workmanship; (b) the Limited Warranty
    requirements have been met (except that the three year limitation of the Limited Warranty does not limit the Power Control Guarantee, which
    is for the lifetime of the Product), and; (c) none of the limitations or exclusions on warranty coverage apply (or than the three year limit),
    CyberPower will (as CyberPower elects, as permitted by law), repair, replace, or pay the Agreed Damage Amount (defined below) for, the
    item(s) of your electronic equipment directly and properly connected to the product (the "Connected Equipment") if that Connected
    Equipment is (x) damaged by AC power line transients, spikes, or surges on properly installed, grounded, and code-compliant 120 volt
    power lines in the United States and Canada, or by transients, surges or spikes on standard telephone equipment lines, or Base 10/100T
    Ethernet lines that are properly installed and connected (a "Power Disturbance") and (y) is directly plugged into and properly connected to a
    CyberPower Product in its original condition which is properly operated when a Power Disturbance passes through the CyberPower Product
    and (y.1) exhausts the protection capacity of the CyberPower Product or (y.2) damages the CyberPower Product. This provision sets out the
    only liability of any character of CyberPower for direct, indirect, special, consequential, and/or incidental damages under our Limited
    Warranty, applies only to Connected Equipment, and all such Liability is limited to the Agreed Damage Amount.
    Making a Power Control Guarantee Claim.
    To make a Warranty claim for damage to Connected Equipment under the Power Control Guarantee, you must do the following:
    1. Complete and return the CyberPower Warranty card or provide reasonable proof of purchase, for example, a sales receipt that
    establishes you as the original end-user consumer purchaser of the Product.
    2. Call CyberPower at (952) 403-9500 or (877) 297-6937 (toll free), write to CyberPower at 5555 12th Ave East, Suite 110, Shakopee, MN
    55379, or e-mail CyberPower at claims@cyberpowersystems.com within ten (10) days of the date of the event for which you wish to make a
    claim for warranty service.
    3. When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have information on
    all applicable insurance or other resources of recovery/payment that are available to the Initial Customer and the name of the power utility
    supplier for the location of the Connected Equipment and Request a Return Materials Authorization (RMA).
    4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the damage
    to the Connected Equipment, and all claim forms that CyberPower provides to you. Show the RMA number on the shipping label or include it
    with the product. You must prepay all shipping costs, must pay the cost of the repair estimate and is responsible for packaging and
    shipment.
    CyberPower's Duties.
    CyberPower will inspect and examine the Product and the item(s) of Connected Equipment (or at CyberPower's election, your written
    statement and repair cost estimate for those item(s)). You must return the product for inspection.
    If the damage to Connected Equipment is covered by the Power Control Guarantee, CyberPower will (in addition to Limited Warranty
    remedies for the CyberPower Product itself) repair (or pay the costs of repair) or replace the Connected Equipment or, at the option of
    CyberPower, as permitted by law, pay to the Initial Customer the "Agreed Damage Amount" (up to the aggregate limits stated below) for all
    item(s) of Initial Customer's Connected Equipment. The "Agreed Damage Amount" for all items of Initial Customer's Connected Equipment
    shall be the lesser of the amount determined under Clause
    (1) or (2) below, reduced by any amounts described in Clause (3) below:
    1. The fair market value of the Connected Equipment as established by the lower of (a) the average price the same or similar items are
    being sold for on E-bay, (b) the price list of Orion
    Blue Book on the date of occurrence (or if such price list is no longer published, a published or announced price list reasonably selected by
    CyberPower), or (c) the lowest price the same or similar items can be purchased for in the United States.
    2. The aggregate ceiling amount for all Connected Equipment: CyberPower OR500 --$35,000; OR700--$50,000
    3. The amount(s) of all payment you have or are entitled to receive from insurance, other warranties, extended warranties, or from other
    sources or persons for the Connected Equipment or damage to such equipment so that CyberPower¡¦s maximum liability shall be reduced to
    reflect all such other payments or sources of recovery
    If CyberPower replaces the connected equipment or pays to the Initial Customer the Agreed Damage Amount, the Initial Customer shall
    transfer all item(s) to CyberPower without warranty by the Initial Customer, but free of lien or other interest.
    CONDITIONS COMMON TO THE LIMITED WARRANTY AND THE POWER CONTROL GUARANTEE
    The Limited Warranty and the Power Control Guarantee are the only and the exclusive express warranty of CyberPower with respect to the
    Product. This exclusion of other express warranties applies to written and oral express warranties.
    LIMITATION: THE LIMITED WARRANTY AND THE POWER CONTROL GUARANTEE DO NOT COVER
    The Limited Warranty and the Power Control Guarantee are intended to exclusive rights and remedies and replace any other rights, to the
    extent allowed by law.
    1. As to the CyberPower Product, the limited warranty does not cover or apply to: misuse, modification, operation or storage outside
    environmental limits for the Products, in transit, in shipment, or in storage, damage or deterioration, improper operation or maintenance, or
    use with items or equipment not designed or intended for use with the product.
    2. As to Connected Equipment, the Power Control Guarantee covers only damage within the specific terms of the Power Control Guarantee
    to Connected Equipment (and only up to the applicable aggregate ceiling amount).
    3. The Power Control Guarantee does not cover damage to Connected Equipment or apply if the Product has been operated in a failure
    mode or not in compliance with CyberPower operating instructions and manuals, or if the Connected Equipment has been operated in a
    failure mode or not in compliance with the instructions and manuals of its manufacturer/vendor.
    The Limited Warranty and the Power Control Guarantee Do Not Apply Unless The Initial Customer:
    1. Has properly connected the Product and the Connected Equipment to properly wired and grounded outlets (including compliance with
    electrical and safety codes of the most
    current electrical code (ANS/NFPA 70), without the use of any adapters, extension cords of other connectors.
    2. Has provided a suitable and proper environment for use and installation of the Product and Connected Equipment.
    3. Has properly installed and operated the CyberPower Product and Connected equipment.
    4. Has operated the Product at all times within the limitations on the Product¡¦s VA capacity as stated in this User Manual.
    CyberPower Does Not Cover or Undertake Any Liability in Any Event for Any of the Following:
    1. Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software.
    2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and code-compliant 120
    volt power lines in the United States and Canada; transients, surges or spikes on standard telephone land lines, PBX telephone equipment
    lines or ethernet lines, when properly installed and connected.
    3. Damage from any circumstance described as excluded above with respect to the product.
    4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the product or
    the Connected Equipment.
    Exclusion of Consequential and Other Damages.
    The sole and exclusive remedies of the Initial Customer are those provided by the Limited Warranty and Power Control Guarantee.
    CyberPower excludes any liability for personal injury under the Limited Warranty and Power Control Guarantee. CyberPower excludes any
    liability for direct, indirect, special, incidental or consequential damages, whether for damage to or loss of property [EXCEPT FOR (AND
    ONLY FOR) the specific limited agreement of CYBERPOWER to provide certain warranty benefits regarding "Connected Equipment" under
    the "CYBERPOWER Power Control Guarantee"], loss of profits, business interruption, loss of information or data. This exclusion applies
    even though damage or loss is caused by negligence or other fault. NOTE: Some States or Provinces do not allow the exclusion or limitation
    of incidental or consequential damages, so the above limitation may not apply to you.
    DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT OR OTHER HIGH RISK ACTIVITIES.
    CyberPower does not sell the Products for use in high-risk activities. The Product is not designed or intended for use in hazardous
    environments requiring fail-safe performance, including the operation of nuclear facilities, aircraft navigation or communication systems, air
    traffic control, weapons systems, life support or medical applications or for use in any circumstance in which the failure of the Product could
    lead directly to death, personal injury, or severe physical or property damage, or that would affect operation or safety of any medical or life
    support device (collectively, "High Risk Activities"). CyberPower expressly disclaims any express or implied warranty of fitness for purpose
    for High Risk Activities.
    CyberPower does not authorize use of any of its products in any High Risk Activity. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF
    A CYBERPOWER PRODUCT.
    The Limited Warranty and the Power Control Guarantee are governed by the laws of the United States and the State of Minnesota, without
    reference to conflict of law principles. The
    application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
    Contact Information: CyberPower's address is 5555 12th Ave East, Suite 110, Shakopee, MN 55379 and its phone number is (952) 403-
    9500 or (877) 297-6937 (toll free). CyberPower is the warrantor under this Limited Warranty. You may also contact CyberPower on the
    Internet at www.cyberpowersystems.com.
    BATTERY REPLACEMENT PROCEDURE:
    1. Remove the right-side of the faceplate.
    2. Remove the three retaining screws on
    the cable protection cover then remove
    the cover.
    3. Disconnect the black and red cable.
    4. Remove the retaining screw of the cable
    connectors.
    5. Replace the new battery pack. Assemble
    the screws, cover, cable and front panel in
    the reverse sequence of above steps.
    Recharge the unit for 4-8 hours to ensure
    the UPS performs expected runtime
    Our new UPS circuit is designed to save energy operating in a GreenPower Bypass Mode.
    A traditional UPS circuit with AVR provides normal output voltage through Relay and AVR transformer.
    The current travels first through the transformer conducting energy and generating heat. This heat
    creates energy dissipation resulting in a "Power Loss" and a loss of utility power and money.
    CyberPower's GreenPower Circuit Design crated a solution to this "Power Loss." When the Utility
    Power is operating normally, our Green Power UPS works in a Bypass Mode. Our GreenPower
    design conducts power only through the Relay and still provides normal output voltage. By saving the
    "Power Loss" when the current travels through the transformer, it can effectively preserve energy and
    cost. When the power line (Utility Power) is abnormal, the UPS will operate under Battery or AVR
    Mode. Under this condition, Green Power UPS and a traditional UPS would operate about the same.
    On average utility power operates normally 88% of the time and the CyberPower GreenPower
    Technology will work in its money/energy saving Bypass Mode.
    4
    1
    5
    2 3
    1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least four hours is recommended to ensure
    that the battery¡¦s maximum charge capacity is achieved. Charge loss may occur during shipping and storage. To recharge the battery,
    simply leave the unit plugged into an AC outlet. The unit will charge in both the on and off position.
    2. If you will use the software, connect the USB cable to the USB port on the UPS.
    3. With the UPS unit off and unplugged, connect the computer, monitor, and any externally powered data storage device (Zip drive, Jazz
    drive, Tape drive, etc¡K) into the battery power supplied outlets. DO NOT plug a laser printer, copier, space heater, vacuum, paper
    shredder or other large electrical device into the UPS. The power demands of these devices will overload and possibly damage
    the unit.
    4. To protect a fax, telephone, modem line or network cable, connect a telephone cable or network cable from the wall jack outlet to the IN
    jack of the UPS. Then connect a telephone cable or network cable from the OUT jack on the UPS to the modem, computer, telephone, fax
    machine, or network device.
    5. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit
    breaker and does not service equipment with large electrical demands (e.g. air conditioner, refrigerator, copier, etc¡K). Avoid using extension
    cords. If used, the extension cord must be grounded and rated for 15 amps.
    Line mode
    Select SW
    Press
    UPS Status Display Capacity Display Digital Value Display
    Initial
    1st
    2nd
    3rd
    4th
    5th(Return)
    Press >3sec
    (Sound Disable)
    Press >3sec
    again
    (Sound Enable)
    (Overload)
    Load
    Cap.
    V
    V
    V
    X
    V
    V
    --
    --
    --
    Output
    Voltage
    V
    V
    --
    --
    --
    Run
    Time
    V
    --
    --
    --
    % of
    Load
    V
    --
    --
    --
    % of
    Batt.
    V
    --
    --
    --
    Battery
    Cap.
    X
    X
    X
    V
    X
    X
    --
    --
    --
    Input
    Voltage
    V
    --
    --
    --
    "V" : Illuminated, "X" : Not Illuminated, "--" : Either
    X
    X
    X
    X
    X
    X
    X
    X
    X
    V
    V
    V
    V
    V
    V
    V
    V
    V
    --
    --
    --
    --
    --
    --
    V
    X
    --
    RUN_TIMEOUTPUTINPUT
    Min
    V
    %
    LOAD BATT. CAP.
    100
    X
    X
    X
    X
    X
    X
    X
    X
    V
    100
    Battery mode
    Select SW
    Press
    UPS Status Display Capacity Display Digital Value Display
    Initial
    1st
    2nd
    3rd
    4th
    5th(Return)
    Press >3sec
    (Sound Disable)
    Press >3sec
    again
    (Sound Enable)
    (Overload)
    Load
    Cap.
    X
    X
    V
    X
    X
    X
    --
    --
    --
    Output
    Voltage
    V
    V
    --
    --
    --
    Run
    Time
    V
    --
    --
    --
    % of
    Load
    V
    --
    --
    --
    % of
    Batt.
    V
    --
    --
    --
    Battery
    Cap.
    V
    V
    X
    V
    V
    V
    --
    --
    --
    Input
    Voltage
    V
    --
    --
    --
    "V" : Illuminated, "X" : Not Illuminated, "--" : Either
    V
    V
    V
    V
    V
    V
    V
    V
    V
    X
    X
    X
    X
    X
    X
    X
    X
    X
    --
    --
    --
    --
    --
    --
    V
    X
    --
    X
    X
    X
    X
    X
    X
    X
    X
    V
    100
    OR500 OR700
    iMac G4 37 - 43 67 - 73
    Desktop PC with 17" LCD Monitor 17 - 23 43 - 49
    Desktop PC with 19" LCD Monitor 15 - 21 34 - 40
    Desktop PC with 21" LCD Monitor 12 - 18 26 - 31
    Desktop PC with 17" CRT Monitor 9 - 15 21 - 27
    6. Depress the power switch to turn the unit on. The power on indicator light will illuminate and the unit will ¡§beep¡¨ once.
    7. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at
    least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the circuit breaker is depressed and
    then turn the UPS on.
    8. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will automatically recharge.
    9. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
    10. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the battery every three months to
    ensure battery life.
CyberPower OR700LCDRM1U

Behöver du hjälp?

Antal frågor: 0

Behöver du hjälp eller har du en fråga om CyberPower OR700LCDRM1U? Ställ din fråga här. Lämna en tydlig och omfattande beskrivning av ditt problem och din fråga. Ju mer information du anger desto enklare blir det för andra ägare av CyberPower OR700LCDRM1U att svara på din fråga.

Se manualen för CyberPower OR700LCDRM1U helt gratis här nedan. Den här manualen tillhör kategorin och har betygsatts av 1 personer med ett genomsnitt på 6.1. Den här manualen är tillgänglig på följande språk: Engelsk. Behöver du hjälp eller har du en fråga om CyberPower OR700LCDRM1U? Ställ din fråga här

CyberPower OR700LCDRM1U – specifikationer

Allmänt
Varumärke CyberPower
Modell OR700LCDRM1U
Produkt Avbrottsfri strömförsörjning (UPS)
EAN 64953271504, 649532715046, 6495327150462, 763615942195
Språk Engelsk
Filtyp PDF
Egenskaper
Uteffekt kapacitet (VA) 700
Uteffekt 400
Energivärdering 1030
Ingångsfrekvens 60
Svarstid (medel) 4
Hörbart larm
Övrigt
Anslutningsdetaljer utgång NEMA 5-15R
Anslutningsdetaljer ingång NEMA 5-15P
Produktstorlek (BxDxH) 438 x 235 x 44.45
Vikt (imperial) 18.5
Omgivningstemperatur vid drift 32 - 95
Dimension (B x D x H) (imperial) 17.25 x 9.25 x 1.75
Batteri
Batteriteknik Slutna blybatterier (VRLA)
Normal drifttid vid halv belastning 11
Normal drifttid vid full belastning 3
Laddningstid 8
Utbytbara batteripatroner BB - HR9-6
Design
Formfaktor -
Certifiering UL1778, cUL 107.1, FCC DOC Class B
Anslutningar
Seriella portar 1
Modem (RJ-11) portar 1
Antal LAN (RJ-45) anslutningar 1
Antal USB 2.0 anslutningar 1
Vikt & dimension
Vikt 8391
Miljökrav
Temperatur vid drift 0 - 40
Intervall för relativ operativ luftfuktighet 0 - 95

Bruksanvisni.ng

Letar du efter en manual? Bruksanvisni.ng säkerställer att du hittar manualen som du letar efter på nolltid. Vår databas innehåller mer än 1 miljon PDF-manualer från över 10 000 märken. Varje dag lägger vi till de senaste manualerna så att du alltid hittar produkten du letar efter. Det är väldigt enkelt: ange bara märket och typen av produkt i sökrutan för att omedelbart semanualen du önskar online helt gratis.