CyberPower PR750LCDRM1U

CyberPower PR750LCDRM1U bruksanvisning

(1)
  • Smart App Sinewave Series
    PR750LCDRM1U/PR1000LCDRM1U
    Users Manual
    K01-0000059-04
    This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Please read
    and follow all instructions carefully during installation and operation of the unit. Read this manual thoroughly before attempting to unpack, install,
    or operate.
    CAUTION! The UPS must be connected to a grounded AC power outlet with fuse or circuit breaker protection. DO NOT plug the UPS into an
    outlet that is not grounded. If you need to de-energize this equipment, turn off and unplug the UPS.
    CAUTION! DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower
    Systems does not sell products for life support or
    medical applications. DO NOT use in any circumstance that would affect operation or safety of any life support equipment, with any medical
    applications, or patient care.
    CAUTION! The battery can energize hazardous live parts inside even when the AC input power is disconnected.
    CAUTION! For pluggable equipment, the socket-outlet shall be installed near the equipment and shall be easily accessible.
    CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of conductive
    contaminants. (Please see specifications for acceptable temperature and humidity range).
    CAUTION! To reduce the risk of electric shock, do not remove the cover, except to service the battery. There are no serviceable parts inside,
    except for the battery.
    CAUTION! To avoid electrical shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a
    computer component.
    CAUTION! DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire, do not use with or near aquariums. Condensation from
    the aquarium can come in contact with metal electrical contacts and cause the machine to short out.
    CAUTION! DO NOT USE WITH LASER PRINTERS! The power demands of laser printers are too large for a UPS.
    UNPACKING
    Inspect the UPS upon receipt. The box should contain the following.
    (1) UPS Unit; (1) User's Manual for UPS; (2) Rack mount Brackets; (1) Emergency Power Off Cable (gray) (1) PowerPanel
    ®
    Business Edition
    Software CD; (1) Serial Interface Cable (DB-9); (1) USB A+B type cable; (1) Warranty Registration Card.
    OVERVIEW
    The PR750LCDRM1U/PR1000LCDRM1U provides automatic voltage regulation for inconsistent utility power.
    The PR750LCDRM1U/PR1000LCDRM1U features 1874 Joules of surge protection, and provides battery
    backup during power outages. The PR750LCDRM1U/PR1000LCDRM1U ensures consistent power to your
    computer system and its included software will automatically save your open files and shutdown your
    computer system during a utility power loss.
    AUTOMATIC VOLTAGE REGULATOR(AVR)
    The PR750LCDRM1U/PR1000LCDRM1U stabilizes inconsistent utility power. The incoming utility power may be damaging to important data
    and hardware, but with Automatic Voltage Regulation, the computer will not experience damaging voltage levels. An Automatic Voltage Regulator
    automatically increases low or decreases high voltage to a consistent, computer safe 110v/120v. The unit powerful sealed lead-acid batteries will
    provide power only if the incoming voltage drops below 80v or increases above 150v.
    SYSTEM BLOCK DIAGRAM
    HARDWARE INSTALLATION GUIDE
    1. Your new UPS may be used immediately upon receipt. However, recharging the battery for at least four hours
    is recommended to ensure that the battery's maximum charge capacity is achieved. Charge loss may occur
    during shipping and storage. To recharge the battery, simply leave the unit plugged into an AC outlet. The unit
    will charge in both the on and off position.
    2. If you will use the software, connect the serial interface cable to the serial port on the UPS and the computer. If
    you would like to use USB cable, please connect the USB cable on the UPS then connect the USB cable to your
    computer.
    3. With the UPS unit off and unplugged, connect your computer, monitor, and any externally powered data
    storage device (Hard drive, Tape drive, etc.) into the battery power supplied outlets. DO NOT plug a laser
    printer, copier, space heater, vacuum, paper shredder or other large electrical device into the UPS. The power
    demands of these devices will overload and possibly damage the unit.
    4. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet). Make sure the wall branch outlet is
    protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air
    conditioner, refrigerator, copier, etc.). Avoid using extension cords.
    5. Depress the power switch to turn the unit on. The power on indicator light will illuminate. If an overload is
    detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and
    unplug at least one piece of equipment from the battery power supplied outlets. Wait 10 seconds. Make sure the
    circuit breaker is depressed and then turn the UPS on.
    6. Your UPS is equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will
    automatically recharge.
    7. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
    8. To store your UPS for an extended period, cover it and store with the battery fully charged. Recharge the
    battery every three months to ensure battery life.
    9. Professional Rack Mount UPS provides one serial port, one dry contact and one USB port to allow connection
    and communication between the UPS and computers or equipment. This allows the simultaneous shutdown of
    two computer systems. Serial port II produces the basic information for equipment that can utilize a dry contact
    ups. The Primary computers (with PowerPanel® Business Edition installed) are the computers that you will use
    to control the UPS and make any changes to the operation of the UPS. When there is a power failure, the
    computer which connects to Primary port will start to shutdown after a user controlled delay. PowerPanel®
    Business Edition will save and close any open files prior to shutting the system down.
    10. EPO (Emergency Power Off) Port:
    The feature is for the application to enable emergency power shutdown. Use the gray cable provided to connect
    the UPS to a normally closed or normally open contact switch according to the circuit diagram. EPO function is
    provided in the UPS. EPO remote switch which is a Push-Back button installed computer room outside by a
    phone line, and not connected any other equipment.
    FRONT / REAR PANEL DESCRIPTION
    1. Power Switch
    Master on/off switch for equipment connected to the UPS.
    2. Power On Indicator
    Indicates the power is on.
    3. LCD Module Display
    LCD shows all the UPS information with icons and messages.
    4. LCD Display Toggle Button
    The button can be used to toggle between different data displays
    on the LCD.
    5. Battery Backup Protected Outlets
    Provides eight battery powered, surge protected and AVR outlets
    for connected equipment and ensures temporary uninterrupted
    operation of connected equipment during a power failure.
    Critical /Non-critical
    When the UPS is overloaded, the circuit breakers will be tripped
    to interrupt the power supply to the uncritical outlets while
    continuing to supply the critical outlets. As well, as the battery
    capacity depletes under the threshold value, the uncritical outlets
    will be shut down and provide energy for critical outlets. The
    threshold can be determined and set by users. Non-critical
    outlets can also be turned on/off manually through the software
    package provided.
    6. Input Power Cord
    Heavy-duty, extra long power cord.
    7. Input Circuit Breaker
    Resettable circuit breakers provide Input optimal overload
    Protection.
    Contact your dealer, or email tech@cpsww.com. Refer to replacement battery pack number RBP422 for PR750LCDRM1U/PR1000LCDRM1U.
    Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery. Service the battery under the supervision of
    personnel knowledgeable of batteries and their precautions. Servicing the battery should only be performed by trained personnel.
    Replacement of batteries located in an OPERATOR ACCESS AREA.
    CAUTION! When replacing batteries, replace with the same number of the following battery: HR9-6(BB) for PR750LCDRM1U/
    PR1000LCDRM1U.
    CAUTION! Risk of Energy Hazard, 6V, maximum 9 Ampere-hour (HR9-6) batteries. Before replacing batteries, remove conductive jewelry such
    as chains, wrist watches, and rings. High energy through conductive materials could cause severe burns.
    CAUTION! Risk of battery explosion, if battery is replaced by an incorrect type. Dispose of used battery according to the instructions.
    CAUTION! To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent protection in
    accordance with the National Electric Code, ANSI/NFPA 70.
    CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
    CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a fire, as they may explode. Follow all local
    ordinances regarding proper disposal of batteries.
    CAUTION! Do not open or mutilate the batteries. Release electrolyte is harmful to the skin and eyes and may be toxic.
    CAUTION! A battery can present a high risk of short circuit current and electrical shock.
    Take the following precautions before replacing the battery:
    1. Remove all watches, rings or other metal objects.
    2. Only use tools with insulated handles.
    3. Do not lay tools or metal parts on top of battery or any terminals.
    4. Wear rubber gloves and boots.
    5. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of ground. CONTACT WITH A GROUNDED
    BATTERY CAN RESULT IN ELECTRICAL SHOCK! The likelihood of such shock will be reduced if such grounds are removed during installation
    and maintenance (applicable to a UPS and a remote battery supply not having a grounded circuit)
    BATTERY REPLACMENT PROCEDURE:
    .
    Line mode
    UPS Status Display Capacity Display Digital Value Display
    Select SW
    Press
    Load
    Cap
    Battery
    Cap
    Input
    Voltage
    Output
    Voltage
    Run
    Time
    % of
    Load
    % of
    Battery
    Initial V X -- X V V
    1
    st
    V X -- X V V
    2
    nd
    V X -- X V V
    3
    rd
    V X -- X V V
    4
    th
    V X -- X V
    5
    th
    (return) V X -- X V V
    (overload) V X -- V -- -- -- -- -- V --
    Battery Mode
    UPS Status Display Capacity Display Digital Value Display
    Select SW
    Press
    Load
    Cap
    Battery
    Cap
    Input
    Voltage
    Output
    Voltage
    Run
    Time
    % of
    Load
    % of
    Battery
    Initial X V -- X V V
    1
    st
    X V -- X V V
    2
    nd
    X V -- X V V
    3
    rd
    X V -- X V V
    4
    th
    X V -- X V
    5
    th
    (return) X V -- X V V
    Press>4sec
    (sound disable)
    X V V X -- -- -- -- -- --
    Press>4sec
    again(sound enable)
    X V X X -- -- -- -- -- -- --
    overload X V -- V -- -- -- -- V --
    “V” illuminated , “X” Not illuminated, “— “ either
    IMPORTANT SAFETY WARNINGS
    INSTALLING YOUR UPS SYSTEM
    1. Remove the right side front panel
    2. Remove the two retaining screws of
    the cable protection cover then remove
    the cover.
    3. Disconnect the black and red cable.
    4. Remove the one
    retaining screws
    5. Charge a new battery pack.
    Assemble the screws cover
    cable and front panel in the reverse
    sequence of above steps. Recharge
    the unit for4-8 hours to ensure the
    UPS performs expected runtime
    LCD STATUS DEFINITION
    BATTERY REPLACEMENT
    8. USB port
    USB communication port for management software.
    9. Serial Port
    Serial port allows connection and communication between the UPS and the
    computer.
    10. SNMP/HTTP Network slot
    Remove the cover panel to install optional RMCARD that allows remote
    monitoring and control your UPS on networks.
    11. Site Wire Fault Indicator
    This LED will illuminate to warn the user that a wiring problem exists within
    the AC receptacle, such as a bad ground, missing ground or reversed
    wiring. If illuminated, disconnect all equipment and contact an electrician to
    ensure outlet is properly wired.
    12. EPO (Emergency Power Off) port
    The interface can be used to connect to switches for emergency power off.
    BASIC OPERATION
    When you first receive the
    unit, plug in the unit to fully
    charge the battery.
    Unplug the unit and turn Power
    Off when first connecting your
    computer and peripherals.
CyberPower PR750LCDRM1U

Behöver du hjälp?

Antal frågor: 0

Behöver du hjälp eller har du en fråga om CyberPower PR750LCDRM1U? Ställ din fråga här. Lämna en tydlig och omfattande beskrivning av ditt problem och din fråga. Ju mer information du anger desto enklare blir det för andra ägare av CyberPower PR750LCDRM1U att svara på din fråga.

Se manualen för CyberPower PR750LCDRM1U helt gratis här nedan. Den här manualen tillhör kategorin och har betygsatts av 1 personer med ett genomsnitt på 7. Den här manualen är tillgänglig på följande språk: Engelsk. Behöver du hjälp eller har du en fråga om CyberPower PR750LCDRM1U? Ställ din fråga här

CyberPower PR750LCDRM1U – specifikationer

Allmänt
Varumärke CyberPower
Modell PR750LCDRM1U
Produkt Avbrottsfri strömförsörjning (UPS)
EAN 649532107506, 6495321075068
Språk Engelsk
Filtyp PDF
Egenskaper
Uteffekt kapacitet (VA) 750
Uteffekt 560
Energivärdering 1780
Ingångsfrekvens 50/60
Svarstid (medel) 4
Hörbart larm
UPS-topologi Line-interactive
Övrigt
Anslutningsdetaljer utgång NEMA 5-15R
Anslutningsdetaljer ingång NEMA 5-15P
Produktstorlek (BxDxH) 438 x 495.3 x 44.45
Vikt (imperial) 40
Omgivningstemperatur vid drift 32 - 95
Dimension (B x D x H) (imperial) 17.25 x 19.5 x 1.75
Batteri
Batteriteknik Slutna blybatterier (VRLA)
Normal drifttid vid halv belastning 23
Normal drifttid vid full belastning 7
Laddningstid 8
Utbytbara batteripatroner BB - HR9-6
Design
Formfaktor -
Certifiering UL1778, cUL 107.1, FCC DOC Class B
Anslutningar
Seriella portar 1
Antal USB 2.0 anslutningar 1
Vikt & dimension
Vikt 18143
Miljökrav
Temperatur vid drift 0 - 40
Intervall för relativ operativ luftfuktighet 0 - 95
Temperaturintervall (förvaring) -15 - 45

Bruksanvisni.ng

Letar du efter en manual? Bruksanvisni.ng säkerställer att du hittar manualen som du letar efter på nolltid. Vår databas innehåller mer än 1 miljon PDF-manualer från över 10 000 märken. Varje dag lägger vi till de senaste manualerna så att du alltid hittar produkten du letar efter. Det är väldigt enkelt: ange bara märket och typen av produkt i sökrutan för att omedelbart semanualen du önskar online helt gratis.